Data Acquisition, Thermography and Magnetic Media

 

Mains Supply and Low Voltage Switch Boards

Requirement:

Main electrical feeds to both a factory, sub distribution panel or production line are vital to the smooth operation of any building, plant or manufacturing process.  Metrum was asked to carry out a Thermographic inspection to a main incoming supply at a 24 hour manufacturing plant for the motor industry.

Solution:

The NEC TH7102MV infrared thermal camera found a localised "hot spot" on the outside of the main switch in one phase.  The problem was immediately highlighted to the Engineering Director, and as a result the circuits were switched to the secondary supply.

Outcome:

As this was a potential fire hazard, Metrum felt that it should be investigated without further delay, and the switch was immediately opened after being isolated.  The hot spot  could be identified as a finger connection which was corroded beyond repair.  Because of the non-intrusive nature of the thermal survey, the problem was located and solved without loss of production.

© Metrum Information Storage Limited

Digital Image

Thermal Image

Back to Application Notes
For further details on Metrum's Thermographic capability, please visit our Thermography page

Home     Data Acquisition     Thermography    Chart Recorders    Magnetic Media     Applications     Diary     Contact Metrum     Metrum