Metrum Information Storage Ltd

Thermal Imaging, Data Acquisition and Magnetic Media



FLIR Industrial Guide Book - Request your free hardcopy now

 

Mains Supply and Low Voltage Switch Boards

Requirement:

Main electrical feeds to both a factory, sub distribution panel or production line are vital to the smooth operation of any building, plant or manufacturing process.  Metrum was asked to carry out a Thermographic inspection to a main incoming supply at a 24 hour manufacturing plant for the motor industry.

Solution:

The NEC TH7102MV infrared thermal camera found a localised "hot spot" on the outside of the main switch in one phase.  The problem was immediately highlighted to the Engineering Director, and as a result the circuits were switched to the secondary supply.

Outcome:

As this was a potential fire hazard, Metrum felt that it should be investigated without further delay, and the switch was immediately opened after being isolated.  The hot spot  could be identified as a finger connection which was corroded beyond repair.  Because of the non-intrusive nature of the thermal survey, the problem was located and solved without loss of production.

© Metrum Information Storage Limited

Digital Image

Thermal Image

Back to Application Notes
For further details on Metrum's Thermographic capability, please visit our Thermography page